IEC 62271-202:2022

Title
Abstract

IEC 62271-202:2022 specifies the service conditions, rated characteristics, general structural requirements and test methods of enclosed high-voltage prefabricated substations. These prefabricated substations are cable-connected to AC high-voltage networks with an operating voltage up to and including 52 kV and power frequencies up to and including 60 Hz. They can be manually operated from inside (walk-in type) or from outside (non-walk-in type). They are designed for outdoor installation at locations with public accessibility and where protection of personnel is provided.
This third edition cancels and replaces the second edition published in 2014. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:
the whole document contents and structure are reviewed with due consideration of IEC 62271-1:2017;
modification of the title and scope to include high-voltage switchgear prefabricated substations;
inclusion of CEADS as a possible component of MV/LV prefabricated substation;
in 7.2.101, the possible influence of surrounding elements on the dielectric performance of high-voltage components as high-voltage switchgear and controlgear and high-voltage interconnections non-metal-enclosed or without earthed screen are now considered;
new informative Annex G with testing procedure to evaluate the impact of solar radiation in temperatures inside the enclosure and how to apply it;
new informative Annex H for appropriate consideration of installation conditions of electronic equipment;
the rated power of a prefabricated substation is now defined as a three-parameter rated value. See 5.101.1;
minimum dimensions for access doors to the prefabricated substation in 6.104.4 and for free height of operation aisle in 6.105.3 have been introduced;
continuous current (temperature rise) test methods have been revised/clarified where necessary;
Figure D.1, which shows the mineral-oil-immersed power transformer load factor inside the enclosure, has been corrected.
The contents of the corrigendum of August 2023 have been included in this copy.

Issue Date

2022-06-22

Category

POW

Included in IECEE System

2023-04-19

Purchase webstore
Test Report Form

No information declared

Testing Equipment List
DISCLAIMER: National differences

The National differences and Group differences, National Deviations and Special National conditions (SNC), are based solely on information provided to the Secretariat by the IECEE Member Bodies and/or NCBs and other sources. The IEC/IECEE is not responsible for, nor will it take any position related to, the accuracy or validity of the information provided. To verify the current status of this type of information, we recommend contacting the Member Body (MB) or National Certification Body (NCB) of the relevant country.

Group Differences are applicable for CENELEC member countries: Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.

No information declared

Id

Name

City

Country

13371

Kista

Sweden

13349

Budapest

Hungary

Id

Name

City

Country

13360

Arnhem

Netherlands