IEC 60099-6:2019

Title
Abstract

IEC 60099-6: 2019 applies to non-linear metal-oxide resistor type surge arresters with spark gaps designed to limit voltage surges on AC power circuits with system voltages Us above 1 kV up to and including 52 kV. This document basically applies to all metal-oxide distribution class surge arresters with internal series and/or parallel gaps and housed in either porcelain or polymeric housings. This second edition cancels and replaces the first edition published in 2002. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
a) A new concept of arrester classification and energy withstand testing was introduced: the line discharge classification was replaced by a classification based on repetitive charge transfer rating (Qrs) and thermal charge transfer rating (Qth). The new concept clearly differentiates between impulse and thermal energy handling capability, which is reflected in the requirements as well as in the related test procedures.
b) Power-frequency voltage versus time tests – with and without prior duty – were introduced as type tests.
c) Requirements and tests on disconnectors were added.
d) Definitions for new terms have been added.
e) Clause 10 contains particular requirements for polymer-housed surge arresters. These are indicated in the form of replacements, additions or amendments to the original clauses or subclauses concerned.
Keywords: testing of metal-oxide surge arresters

Issue Date

2019-05-22

Category

PROT

Included in IECEE System

2021-02-08

Purchase webstore
Test Report Form
Testing Equipment List
DISCLAIMER: National differences

The National differences and Group differences, National Deviations and Special National conditions (SNC), are based solely on information provided to the Secretariat by the IECEE Member Bodies and/or NCBs and other sources. The IEC/IECEE is not responsible for, nor will it take any position related to, the accuracy or validity of the information provided. To verify the current status of this type of information, we recommend contacting the Member Body (MB) or National Certification Body (NCB) of the relevant country.

Group Differences are applicable for CENELEC member countries: Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.

No information declared

Laboratory Name

City

Country

Responsible National Certification Body

Shaanxi

China

Id

Name

City

Country

13349

Budapest

Hungary

Id

Name

City

Country

28154

Nairobi

Kenya