| IEC 60598-1:2003 (ed.6) | ||||
| Clause | Subject | Keywords | Sheet | |
| General | Metallic paint |
- § 6.1 - IEC 60238 - Metallic paint |
006/06 | |
| General | LEDs used as a light source in luminaires |
- LEDs - Harmful radiation - Light intensity |
003/06.m | |
| General | Luminaires system for 230V |
- luminaires system - Extra low voltage - IEC 60598-2-23 |
001/06 | |
| General | IEC 62262/EN 50102 |
- IEC 62262 EN 50102 - IK code - Degrees of protection |
002/06 | |
| General | Luminaires for the use with independent control gear |
- Independent lamp control gear - §§ 1.2.29 - 3.2 - 3.3.1 12.4.1 h) - Information, advice |
127/06.m | |
| General 1.7 | Fixed luminaire with track |
- IEC 60570 - 6,5 mm - Track system |
004/06 Figures |
|
|
General – 1.7 |
Fixed luminaire with track |
- IEC 60570 |
DSH 809 | |
| General Section 12 | Luminaires provided with LEDs |
- Control gears - Section 12 - IEC/EN 60825-1 |
005/07 | |
| 0.2 |
- Socket-outlet mounted - Rechargeable luminaire - Rechargeable lamps |
- Socket outlet - Transformer/Plug - Battery chargers |
007/06 | |
| 0.3.1 | Portable floodlights lighting chains IP44 |
- Plug - Full-profile - Outdoor use |
008/06 | |
| 0.4 | Floodlight with mounting accessories |
- Floodlight - Mounting accessories - Part of installation |
009/06 Figures |
|
| 0.4.2 | Luminaires needing assembly by the user |
- Common sense - Easiness of connection - Pendant luminaires |
011/06 | |
| 0.4.2 | Instruction manual of a floodlight |
- Mounting instructions - Unfavourable - Instructions manual |
010/06 | |
| 0.4.2 and 12 | Luminaires needing reconnection by the installer |
- Reconnection - Extra terminal - Different voltages or wattages |
012/06 | |
| 0.5 | Use of 230V components in 240V luminaires |
- Lamp control gear - 230 V, 240 V - Rated voltage |
013/06 | |
| 0.5 | Series - compensated luminaire (working voltage) |
- Series capacitors - 450V - Working voltage |
014/06 | |
| 0.5 | Connecting device with fuse holder |
- Fuse holder - Connecting device - Fuse |
015/06 | |
| 0.5 | Luminaire marked for lamp GU 5,3 |
- EPCAP Group - GU 5,3 - GX 5,3 connector |
016/06 | |
| 0.5 |
Completion of Test Report Formats (TRF's) and use of Annex 1 Table of components |
- Components - Certification - TRF |
017/06 | |
| 0.5.2 | IP 55 handlamp |
- IP classification - Plug - IP 44 |
516/06 | |
| 1.2.60 | T8 to T5, T8 to T8 and similar lamp adaptors (including ditto with LED) |
- Retro-fit conversion units - Semi luminaires - Lamp adaptors |
DSH 702 | |
| 2.2 | T8 to T5, T8 to T8 and similar lamp adaptors (including ditto with LED) |
- Retro-fit conversion units - Semi luminaires - Lamp adaptors |
DSH 702 | |
| 3 | Definition of basic type reference |
- Rated wattage - Type reference - Separately marked |
018/06 | |
| 3 | Marking of lamp types according to IEC TS 61231 |
- ILCOS codes - IEC TS - Test Reports |
019/06 | |
| 3 |
Marking on class III luminaires “system” |
- Each connection - Marking |
020/06 Figures |
|
| 3.2 |
Marking on small luminaires |
- Marking - Small luminaires - Supply cord |
021/06 | |
| 3.2.2 | Rated voltage marking |
- Filament lamps - Rated voltage - Marking |
022/06 | |
| 3.2.6 | Marking with IP numbers |
- IP marking - Mounting orientations - Type designation |
023/06 | |
| 3.2.6 | “IP X8” marking |
- Marking - Table J.2 - IP X8 |
024/06 | |
| 3.2.6/9.2 | IP test on recessed luminaires |
- Test recess - Fixed luminaire - Recessed luminaire |
025/06 | |
| 3.2.6 / 9.2 | IP test on recessed luminaires |
- Test recess |
DSH 0834 | |
| 3.2.8 | Lamp-type information marking |
- Manufacturer - Marking plate - Instructions |
026/06 | |
| 3.2.13 | Symbol for minimum distance from lighted objects |
- Teperature - Lighted object - Distance symbol |
027/06 | |
| 3.2.16 | Protective shields |
- Marking - Glass - Plastic - Protective shield |
028/06 | |
| 3.3 |
Markings / additional information |
- Proper installation - Safety - Markings |
029/06 | |
| 3.3.7/4.24 | UV radiation |
- Protected shield - UV blocked lamp - Mounting height |
030/06 | |
| 4.2/8.2.1 | Luminaire with fuse holder/fuse |
- Entrance - Tool - Marketing |
031/06 | |
| 4.2/15.7 | Non-detachable flexible cable or cord |
- Components - Conductors - Cable or cord |
032/06 | |
| 4.4.4 | Lampholder fixed by the shade ring |
- Luminaire standards - Lampholder - Shade ring |
033/06 | |
| 4.4.4 ii) | Lampholder mounting brackets |
- Lampholder - Safety - Compliance |
034/06 | |
| 4.7.2 | Supply terminals (8 mm free wire) |
- Figures 1, 2, 3 - Correct way - Both wires stripped 8 mm |
035/06 figures |
|
| 4.7.3 | Lampholder terminals |
- Screwless terminal - Rewirable luminaire - Solid/flexible conductors |
036/06 | |
| 4.7.4 | Terminals for internal and external connections |
- Internal connections - Supply connection - Internal wiring |
037/06 | |
| 4.8 | Switches for luminaires |
- Switches - 10.000 cycles - IEC 61058-1 |
038/06.m | |
| 4.10 | Insulation required for external and SELV wiring |
- Basic insulation - Double/reinforced insulation - Wiring |
039/06 | |
| 4.10.1 | Metal suspension device |
- Suspension device - Metal hook - Fixed installation |
040/06 | |
| 4.10.1 | Double and reinforced insulation |
- Enclosure - Mounting surface - Live parts |
041/06 | |
| 4.11.1 | Contact pressure |
- Constuction - Each case - Touch lamp |
042/06 | |
| 4.11 - 4.12 | Luminaires to be assembled by user |
- User - Earth connection - Ready-made plugs and connectors |
043/06 | |
| 4.11.3 | Locking device for screws |
- Locking device - Mechanical connections - Fixing screws |
044/06 | |
| 4.11.3 | Screw connections |
- Small "spikes" - Locking of screw connections - Ballast |
045/06 Figure |
|
| 4.11.3 | Electrical connections |
- Construction - Connections - Locking device |
046/06 figures |
|
| 4.11.3/7.2.4 | Rivets for electrical and mechanical connections |
- Rivets - Earthing connections - Accidental loosening |
048/06 | |
| 4.11.3 and 7 | Crimped connections |
- Relevant tests - Crimped connections - Mechanical / electrical contacts |
047/06 figures |
|
| 4.11.4 | Material with equivalent characteristics |
- Material - Equivalent characteristics - Conductive material |
049/06 | |
| 4.11.5 | Wooden parts on luminaires |
- Wooden parts - Contact with current carrying parts - Supplementary insulation |
050/06 | |
| 4.12.4 |
Portable luminaire; different parts can be loosen by hand |
- Middle pipe - Adequate means - Clause 4.12.4 |
051/06 | |
| 4.13.1 | Mechanical strength |
- Mechanical strength - Light source - Not performed |
052/06 | |
| 4.14 | Suspension devices |
- Additional weight - Point B and/or C - Design |
053/06 Figure |
|
| 4.14 | Suspension devices for recessed luminaire |
- Fixed luminaires - Fixing devices - Test A |
054/06 | |
| 4.14.1 | Clip-mounted luminaire |
- Clip-mounted luminaire - Unfavourable condition - Normal use |
055/06 | |
| 4.14.1 | Clip-mounted luminaire: pulling test |
- Clip-mounted luminaire - No movement - Unfavourable direction |
056/06 Figure |
|
| 4.14.3 | Screw adjustable by the user |
- Instruction manual - More than 360° - User |
057/06 | |
| 4.15 and 12.7.1 | Application of clauses 4.15 and 12.7.1 |
- Ballast - Plastic enclosure - Metal “body” |
060/06 | |
| 4.15 | Application of the linear regression formula |
- Both materials - Thermo-resisting bush - Thermoplastic body |
061/06 | |
| 4.15 | Flammable materials |
- Ignition temperature - Life time - Glow wire test |
058/06 | |
| 4.15 | Heated part |
- Light sources - Ballasts - Transformers |
059/06 | |
| 4.15 a) | Luminaires in thermoplastic material (fixing points) |
- Ballast - Constructive measures - § 4.15 a) / § 12.7.1 |
062/06 Figure 1 Figure 2 |
|
| 4.16 | Temperature sensing control device |
- Reproducibility - Additional fixing - Ballast or transformer |
063/06 | |
| 4.16.2 | “Temperature sensing controls” |
- Temperature sensing device - PTC or fuse - Transformer and ballast |
064/06 | |
| 4.24 | Annex P |
- Lamp manufacturers - Information - Case by case |
065/06 | |
| 4.24 | Annex P |
- Data - Manufacturer - Procedure A |
066/06 | |
| 4.24 | Use of different M.H. lamps |
- ILCOS code - Rated current - New lamp |
067/06 | |
| 4.24 | Protective shield |
- LUMEX - Lamp manufacturers - Technical information |
068/06 | |
| 4.24 | Annex P |
- Lamp manufacturers |
DSH 0873 | |
| 5.2 | Non standardised plug for class III luminaire |
- Sub clause 4.11.6 - Marking - Rated current |
069/06 | |
| 5.2.2 | Insulation required on a cable (SELV) |
- Basic insulated parts - SELV - Plug-in transformer |
070/06 | |
| 5.2.2 | External wiring for low voltage luminaire |
- Sub clause 5.2.2 - Standard - External wiring |
071/06 | |
| 5.2.2/5.3.5 | Internal wiring for ordinary luminaire |
- Internal cable - Cord anchorage - Cable length |
072/06 | |
| 5.2.2/7.2.11 | Transparent flexible cords |
- Transparent cable - Earth wire - Green/yellow |
073/06 | |
| 5.2.10 | Cord anchorage |
- External wiring - Cord anchorage - Precautions |
129/07 | |
| 5.2.10/5.3.5 | Cord anchorage on lampholder |
- Class I/ II/ III - Live parts - Lampholder |
074/ 06.m | |
| 5.2.10/5.3.5 | Cord anchorage on adjustable luminaire |
- Cord anchorage - Adjustable - Cable length |
075/06 | |
| 5.2.10/5.3.5 | Recessed luminaire delivered with separate control gear |
- Complete cord anchorage - Sub clause 5.3.5 - Separate control gear |
076/06 | |
| 5.2.10.2/5.2.10.3 | Cord anchorage with type Yor Z attachment on Printed Circuit Board |
- Cord anchorage - Soldered connection - Type Y or Z attachment |
077/06 | |
| 5.2.16 | Connectors / screwless terminals |
- Clause 4.11.6 - Appliance inlets - Connectors |
521/06 | |
| 5.3 | PTFE basic insulated cable |
- 0,6 mm - PVC and rubber - High voltage test |
078/06 | |
| 5.3 | Internal wiring for some lamp circuits |
- Internal wiring - Electric strength - Component |
079/06 | |
| 5.3.1 | Through wiring in the luminaires |
- Luminaire manufacturer - Skilled persons - Cable/wiring |
080/06 | |
| 5.3.3 | Use of additional sleeves |
- Construction - Sleeve - Bushings |
081/06 | |
| 7.2 | Locking on earthing connection |
- Construction - During mounting - Spacers |
082/06 Figure |
|
| 7.2.1 | Earthing in luminaire system |
- Metal body - Each luminaire - Fixed installation |
083/06 | |
| 7.2.1 | Provisions for earthing |
- Screws connection - Installation - Cleaning |
084/06 | |
| 7.2.1 | Electrical connections |
- Mechanical stress - Terminal block - Earth connection |
085/06 | |
| 7.2.4 | Reliability of the earthing circuit |
- Drawing - Way of earthing - Snap-in pins |
086/06 Figure |
|
| 8 | Standard test finger |
- Cross-section area - External connection - Lampholder terminals |
087/06 | |
| 8 | IP protection of recessed parts |
- Paragraph 8 - IP classification - Item 12.3 |
501/06 | |
| 8.2.1 | Live metal parts projected from Edison screw caps |
- Protection against electric shock - Live metal parts - Standard test finger |
090/06 | |
| 8.2.1 | Built in components accessibility |
- 50mm test sphere - IEC 60598-1 - Built in components - Accessible part - 34D/784/CD- Proposal "S" |
088/06 | |
| 8.2.1 | Luminaires with LEDs |
- Sub clause 8.2.1 - Lamp compartment - Two lines of defence |
DSH 089/06m | |
|
8.2.1 8.2 Standard Sheet 7005-56-2 |
G10q - connector's construction |
- G10q lampholder - Connector's construction - Protection against electric shock |
091/06.m Figure 1 Figure 2 Figure 3 |
|
| 8.2.3 | Class II luminaire with metal reflector |
- Distance - Metal reflector - Lamp replacement |
092/06 | |
| 8.2.3 | Metal fixing devices for components |
- Live parts - Reinforced insulation - Fixing device |
093/06 | |
| 8.2.3 | Class I/ class II luminaires protection against electric shock |
- D.S. N° 103/05 - Basic insulation - Standard test finger |
094/06 Figure |
|
| 8.2.3 | Luminaire with GZ12 lamp cap |
- PGZ12 - Metal part of the lamp cap - Class II luminaire |
DSH 703 | |
| 8.2.5 | Class II luminaire for discharge lamps |
- Constructions - Common sense - LUMEX |
095/06 Figure |
|
| 9 | IP 65 luminaires |
- All parts - Instructions - Gasket |
096/06 | |
| 9 | IP 20 luminaires |
- Instruction leaflet - Indoor/oudoor - Glands |
097/06 | |
| 9/9.2 | IP X3 and X4 test |
- Ceiling - IP X1 / X2 - More than 10 mm |
098/06 | |
| 9.2.0 | IP 40 |
- IP 40 - Luminaire enclosure - No entry - IEC 60529 |
DSH 701 Figures |
|
| 9.2 | Torque for fixing screws of covers |
- Instructions - Manufacturer - Table 4.1 |
099/06 | |
| 9.2 | IP ratings |
- Mounting board - 10 mm overhang - IP X3 / X4 |
100/06 | |
| 9.2 | Test for ingress of moisture |
- IP X3 / X4 - Quality of the lamp - Conformity |
101/06 | |
| 9.2f | Entry of test probes for IP 3X and 4X |
- IEC 60529 - Enclosure - Drain holes |
102/06 Figure 1 Figure 2 Figure 3 Figure 4 |
|
| 10 | Dielectric strength test on bushing |
- Class I - II - Bushings - Double insulated cable |
103/06 Figure |
|
| 11 | Distances inside a lamp |
- Heating tests - Creepage distances - Components |
104/06 | |
| 11 | Rule for creepage across grooves and similar surface discontinuities |
- Creepage - Grooves - Conducting path - Shortest distance - Through air |
590 | |
| 11 | Supply terminals-creepage distances and clearances |
- Supply terminals - 8 mm test - Creepage distances and clearances |
128/07.m | |
| 11 | Touch lamp |
- Touch lamp - Controllers - Capacitors |
DSH 704 | |
| 11 & Annex M | Measurements of creepage distances and clearances |
- Maintenance - Live parts - Capacitor case |
105/06 | |
| 11.2 | Creepage and clearances between a metal reflector and the cap of a fluorescent lamp |
- Basic insulation - Metallic lamp cap - Metal reflector - Class II luminaires |
106/06 Figure |
|
| 11.2.1 | Creepage distances and clearances at a supply terminal |
- Lampholders - § 11.2.1 - Supply terminal |
108/06 | |
| 11.2.1 | Pendant luminaire with a "ceiling cone" |
- Mounting surface - Supply wires - Ceiling cone - Metal encased - Class II |
107/06 | |
| 12 | Heating tests for tungsten halogen lamps |
- Highest temperature - Warning notice - Luminaire |
110/06 | |
| 12 | Endurance and thermal tests on appliances for purifying water using an UV lamp |
- Thermal tests - Abnormal conditions - Temperature of water flowing |
109/06 | |
| 12 | Endurance and thermal tests |
- Clause 12 - IR - Time limited controls |
111/06 | |
| 12.1 | Temperature limits of the external parts (metal) of a fixed luminaire |
- Metal part - 70°C - Fixed luminaire |
112/06 Figure |
|
| 12.4 | Clarification of some luminaire parts |
- Handles, knobs - Hand lamps - § 3.3 -IEC 60598-1 |
113/06 | |
| 12.4.1 | Temperature limit on terminal block |
- Terminal block - T marking - Clauses 13-14-15 |
114/06 | |
| 12.4.2 | Sleeve for earthing supply cable |
- Supply cable - Sleeve - Earthing conductor |
115/06 | |
| 12.5.1 | Abnormal operation condition |
- IP 00 transformer - IEC 61558-1 - Short-circuit test |
116/06 | |
| 12.5.1.4) | Luminaire inoperative after the test |
- Clauses 0.3-12.5) - SELV - Inoperative luminaire |
117/06 | |
| 12.5.1a)4) | Requirements for convertors |
- Transformers - Convertors - Requirements |
118/06 | |
| 12.6.2 | “Temperature sensing controls” |
- Temperature sensing device - PTC or fuse - Transformer and ballas |
064/06 | |
| 12.7 | Temperature extrapolated value |
- The graph - Fixation points - Ball pressure test |
119/06 | |
| 12.7.1 | Fault condition test |
- Normal operation - Mounting screws - Sub-clause 12.6 |
120/06 | |
| 12.7.1 | Application of clauses 4.15 and 12.7.1 |
- Ballast - Plastic enclosure - Metal “body” |
060/06 | |
| 12.7.1 | Application of the linear regression formula |
- Both materials - Thermo-resisting bush - Thermoplastic body |
061/06 | |
| 12.7.1 | Luminaires in thermoplastic material (fixing points) |
- Ballast - Constructive measures - § 4.15 a) / § 12.7.1 |
062/06 Figure 1 Figure 2 |
|
| 13.2.1 | Ball pressure test on soft thermoplastic |
- Ball pressure test - Thermoplastic materials - Reinforced insulation |
121/06 | |
| 13.2.1 | Temperature for ball pressure test |
- Temperature - Hottest point - Inner surface |
122/06 | |
| 13.3.1 | Needle flame test / glow wire test |
- Needle flame - Glow wire (650°C) - Burning drops |
123/06 | |
|
20.12.3 Tables 12.1 - 12.2 |
Bridging test |
- Normal operation - Bridging test - Tables 12.1 – 12.2 |
534/06 | |
| Annex A | Push-on lampholders |
- Push-on lampholder - New lamps - Live parts |
124/06 | |
| Annex C | Self-ballasted lamps luminaires |
- Abnormal condition - 240 hours - Self ballasted lamps |
125/06 | |
| Annex C | Luminaires for M.H lamps |
- Rectifying effect - Declaration - Certification Body - Updated Table |
126/06 Table.rect.effect.zip |
|
| Annex M | Measurements of creepage distances and clearances |
- Maintenance - Live parts - Capacitor case |
105/06 | |